行业新闻
镀锌螺旋风管安装规定
镀锌螺旋风管安装规定
Installation regulation of galvanized spiral air duct
1、镀锌螺旋风管水平安装,直径或长边尺寸小于等于400mm,间距不应大于4m;大于 400mm,不应大于3m。螺旋镀锌螺旋风管的支、吊架间距可分别延长至5m 和3.75m;对于薄钢板法兰的镀锌螺旋风管,其支、吊架间距不应大于3m。
1. Galvanized spiral duct installed horizontally, diameter or long side size is less than or equal to 400 mm, spacing should not be greater than 4 m; more than 400 mm, should not be greater than 3 m. The spacing of support and hanger of spiral galvanized spiral duct can be extended to 5 m and 3.75 m respectively, and for galvanized spiral duct with thin steel plate flange, the spacing of support and hanger should not be greater than 3 m.
2、镀锌螺旋风管垂直安装,间距不应大于4m,单根直管至少应有2 个固定点。
2. Galvanized spiral air duct should be installed vertically, the distance should not be more than 4m, and a single straight pipe should have at least two fixed points.
3、镀锌螺旋风管支、吊架宜按国标图集与规范选用强度和刚度相适应的形式和规格。对于直径或边长大于2500mm 的超宽、超重等特殊镀锌螺旋风管的支、吊架应按设计规定。
3. Galvanized spiral duct support and hanger should be in accordance with the national standard atlas and the selection of strength and rigidity in accordance with the specifications of the form and specifications. Supports and hangers of special galvanized spiral ducts with diameters or edges longer than 2500mm, such as super wide and overweight, shall be designed according to the regulations.
4、支、吊架不宜设置在风口、阀门、检查门及自控机构处,离风口或插接管的距离不宜小于200mm。
4. The support and hanger should not be set at the tuyere, valve, check door and automatic control mechanism, and the distance from the tuyere or nozzle should not be less than 200 mm.
5、当水平悬吊的主、干镀锌螺旋风管长度超过20m 时,应设置防止摆动的固定点,每个系统不应少于1 个。
5. When the length of main and dry galvanized spiral duct of horizontal suspension exceeds 20m, the fixed point should be set to prevent swing, and each system should not be less than one.
6、吊架的螺孔应采用机械加工。吊杆应平直,螺纹完整、光洁。安装后各副支、吊架的受力应均匀,无明显变形。镀锌螺旋风管或空调设备使用的可调隔振支、吊架的拉伸或压缩量应按设计的要求进行调整。
6. The hole of the hanger should be machined. The hanger should be straight and threaded with integrity and cleanness. After installation, the force of each auxiliary branch and hanger should be uniform without obvious deformation. The tension or compression of the adjustable vibration isolation support and hanger used in galvanized spiral air duct or air conditioning equipment shall be adjusted according to the design requirements.
7、抱箍支架,折角应平直,抱箍应紧贴并箍紧镀锌螺旋风管。安装在支架上的圆形镀锌螺旋风管,应设托座和抱箍,其圆弧应均匀,且与镀锌螺旋风管外径相一致。
7, hoop brackets, folding angle should be straight, hoop should be tightly and tightly tightened galvanized spiral duct. The circular galvanized spiral air duct installed on the bracket shall be provided with a bracket and a clamp, and the arc shall be uniform and in accordance with the outer diameter of the galvanized spiral air duct.
8、检查数量:按数量抽查10%,不得少于1 个系统。
8, the number of inspections: according to the number of spot checks 10%, no less than 1 systems.
9、检查方法:尺量、观察检查。
9, the inspection methods: ruler measurement, observation and inspection.